Modular Meter Inputs
The U1604 summator can be equipped with up to 64 electrically isolated S0 meter inputs in a modular fashion for processing pulse-shaped (S0) input signals or with analog inputs for recording analog signals.
The SU1624 pulse input module and SU1634 analog input module is used for this purpose.
LON Meter Inputs
Up to 64 LON devices can be connected to the U1604 summator via the easy-to-wire, reverse polarity protected, electrically isolated LON interface.
Evaluation
All relevant energy and consumption data are acquired over predefined periods of time at a programmable interval using 64 processing channels (interval / measurement data list), and are stored as a load profile along with respective maximum values.
Data Recorder
Up to four recorders with a maximum of 64 channels and various time bases as of one second can be defined in addition to the interval / measurement data list. Any desired data can be selected for each channel (analog values, power values, consumption values per interval and overall meter readings) and saved as 32 bit float values (default) or 64 bit double values. A total of 100 MBytes of rotating memory capacity is available.
Ethernet Interfaces (100 Mbit/s)
The Ethernet interface permits remote access to device data via a TCP/IP network. Up to four TCP/IP sockets with ECL access can be used simultaneously (corresponds to 4 previously used COM servers).
An ECS LAN network can also be implemented via two of These sockets (ECS LAN via COM).